Configuring Alarm State Aggregation
- Last UpdatedApr 22, 2022
- 1 minute read
Configuring alarm state aggregation consists of normal alarm configuration procedures plus an added step of enabling the aggregation feature on each relevant Area object.
Note: Alarm aggregation is enabled by default on Area objects. Alarm aggregation cannot be disabled on application objects, such User Defined objects.
To configure alarm state aggregation
-
Accept the default settings or configure alarm severities for each of the four severity levels you want to aggregate. This is a global configuration.
-
Configure an object with one or more alarms. All alarms configured on all objects will be aggregated.
-
Set the AlarmModeCmd of the object to enabled or silenced, but not to disabled.
-
Set the AlarmModeCmd of at least one alarm on the object to enabled or silenced, but not to disabled.
-
Set the AlarmModeCmd of the Area object to enabled or silenced, but not to disabled.
-
Check the Aggregate Alarms checkbox on the Area object editor to enable alarm aggregation. This sets the value of the AlarmAggregationStateCmd attribute to True.
